GE EntelliPro ES Series Installation And Instruction Manual page 160

Motor controller
Table of Contents

Advertisement

CHAPTER 4: COMMUNICATION
 
 
 
 
Holding
Modbus
Register
Size
113
16 bit
ForceLocalRemote switch
Bit 0: for local switch on Class1 failure.
bit 1 - bit 3: Free
bit 4 - bit 6 : Force local/remote switch to
remote on Modbus Failure
bit 7: Free
114
16 bit
Protection - Inputs Enable / Disable
bit 0 - Overload
 
115
16 bit
Remote Source & Local Remote Switch control
 
116
16 bit
Bus Command Configuration
 
 
117
16 bit
Hardwire Configuration
NOTE:
Registers 115, 116 and 117 must be programmable sequentially, in order to get the expected configuration.
Individual configuration of these registers will not give the expected configuration behavior.
4.23
 
Variable
bit 1 - Phase LossL
bit 2 - GF
bit 3 - UnbalancedLoad
bit 4 - Thermistor
bit 5 - EmergencyStop
bit 6 - LimitSwitch
bit 7 - SafetyCircuit
bit 8 - MainCircuit
bit 9 - ControlCircuit
bit10 - SwitchPosition
bit 11 - UnderLoadCurrent
bit 12 - OverloadCurrent
bit 13 - ExternalSupervision
bit 14 - CyclicCommunicationLoss
bit 15 - LongStartTime
Bit 0 - bit 2
1 - class1
2 - Modbus
3 - Hardwire
Bit 4 - bit 6
1 - class1
2 - Modbus
3 - Hardwire
4 - Fixed Local
5 - Fixed Remote
bit 0 - Class1 enable/ disable
bit 1 - Class1 n bit 0r (n+1) bit
bit 2 - level/edge
bit 3 - Inverted OFF / Non-Inverted OFF
bit 4 - Class2 Enable/disable
bit 5 - reserved
bit 6 - Modbus Enable/disable
Bit 0 - hardwire enable/ disable
bit 1 - hardwire n bit 0r (n+1) bit
bit 2 - hardwire level/edge
Description
Switch setting upon Modbus and/or Profibus
class1 Bus failure
0 = None - Switch remains as is
1 = Local on Profibus Class 1 failure
 
0 - None
1 - Local on Modbus failure
2 - Remote on Modbus failure
3 - OFF
0 = Disable
1 = Enabled
Example:
If overload protection on holding register 64
is set to failure and this bit is set to 0, then the
overload failure is ignored.
If overload protection on holding register 64
is set to alarm, and this bit is set to 0, then the
overload alarm is ignored.
If overload protection on holding register 64
is set to failure and this bit is set to 1, then the
overload failure is activated.
If overload protection on holding register 64
is set to alarm, and this bit is set to 1, then the
overload alarm is activated.
This is applicable for the Bit 1 thru Bit 15
 
Bit0 thru Bit2 defines the Remote source
 
 
 
Bit4 thru Bit6 defines the source that controls
the local/remote switch selection.
 
Note: Fixed local is defined as Hardwire,
Modbus, Profibusand 2
Enables the EntelliPro ES controls (ON/OFF/
Reset...) by different protocols
If Profibus DP Class 1 is enabled then bits 1,2,3
must be set per the required operation
 
 
Enables Profibus DP class 2 protocol to control
the motor
 
Enables Modbus protocol to control the motor.
Allow EntelliPro ES control via hardware
 
If Bit 0 is enables (2), bit 1 and 2 must be set
EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
Min
Max
Step
Units
0
127
1
 
 
0
65535
1
 
 
0
127
1
 
 
0
127
1
 
 
5
0
 
 
Scale
Format Default
Unsigned
10
integer
Unsigned
65471
Integer
Unsigned
34
Integer
Unsigned
92
integer
Unsigned
10244
integer