CHAPTER 4: COMMUNICATION
4.2.3 Profibus Interface
The EntelliPro ES supports DPV0 and DPV1 protocols, which is comprised of Cyclic and Acyclic data transfer.
The external connections through the Profibus interface (female D-sub connector) are as follows:
D-Sub Connector Pin
Table 4.10 Profibus interface external connections
The Communication LED indicates the status of Profibus interface:
LED
Communication
Table 4.11 Profibus LED indications
When used for Profibus, the Fieldbus port has the following characteristics:
Baud rate: 9600, 19200, 93750, 187500, 500000, 1.5M, 3M, 6M and 12M bps (with autodetect)
Address: 1 to 125 – settable through the front switches. Switches setting above 125, will default to
126.
Vendor ID: 0x500E
Data table size: Max_Data_Len = 162, Input_Data_Len = 144 bytes, Output_Data_Len = 18 bytes
The Profibus DP Master must read the GSD (Device Master Data) file of the EntelliPro ES for the purposes of
configuration and parameterization. The GSD file for the EntelliPro ES is named GE500E.GSD and it is
available on the WinESG
4.35
V–
L
H
V+
Color
Random flashing amber
Flashing one second ON
CD.
Connection (external device)
Pin 5
Pin 8, line A (negative TX/RX)
Pin 3, line B (positive TX/RX)
Pin 6
Solid amber
No Profibus or Modbus communicatio
one second OFF
EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
Description
Cyclic communication ok
Acyclic communication / Modbus
communication
n
or communication error