CHAPTER 5: WinESG
 
5.3.2.4 Parameterization Function panel
The function panel provides a means to define motor operation during start-up, enable the debug screen, and select
the type of parameterization. Refer to figure 5-10 for the WinESG parameterization function panel.
Figure 5-10-: WinESG parameterization function panel
Parameterization definition:
Parameterization
Parameterization
Mode 1:
Disabled
Enabled
Disabled
Enabled
Status updates on debug window: allow viewing of logic variables in the debug panel
CAUTION:
Debug panel should only be enabled for testing purpose. On normal operation It should be disabled.
5.19
 
Mode 2:
Disabled
Parameterization allowed only when motor is in stop condition
Disabled
Parameterization allowed via Profibus while motor is at any
state.
Enabled
Parameterization allowed via Profibus when draw out position
is not in test or operation mode
Enabled
Parameterization allowed via Profibus when the operation
mode is not Remote or Local.
Operation
EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL