3.1.5 Overload protection n-times reset

 
EntelliPro ES has an n-times automatic reset function, which allows a defined number of automatic reset operations.
The reset count will be automatically cleared when one hour elapses from the last overload trip.
 
The n-times can be set in the WinESG parameterization/alarm panel shown in the illustration below, or Modbus
function code 6 register 45.
 
Figure 3-11 shows an example of the auto-reset count operation. In this particular example the auto reset is set
to 2.
 
 
 
OL Trip
Auto
Reset 1
 
 
 
 
t = 0
t=1
 
 
 
Figure 3-11 EntelliPro Auto-reset operation
 
 
 
For an ATEX configured device, the Auto-Reset parameter can be set to four different values: 0, 1, 2, and 3.
For a non-ATEX configured device, the values allowed are from 0 to 65535. However any value greater than 3 indicates
that Auto-Reset is always allowed.
 
When the auto-reset parameter is set to 0, the auto-reset is disabled and a manual reset is required after an overload
trip.
 
EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
 
 
OL Trip
OL Trip
Auto
Manual
Reset 2
Reset 1
t=2
t=3
Time (minutes)
CHAPTER 3: MOTOR PR OTECTION
 
Auto Reset
allowed after
1 hour of last
reset (at -T=3)
t=n
3.15