2.1.2 Electrical installation

 
This section describes the electrical installation of the EntelliPro ES motor relay.
 
 
CAUTION:
EntelliPro ES is not to be used in any way other than described in this manual.
 
 

2.1.2.1 Power supply connection

 
EntelliPro ES3 DP 2 0 and EntelliPro ES5 DP 2 2 are 24Vdc supply input versions, while EntelliPro ES3 DP 3 0,
EntelliPro ES5 DP 3 2, and EntelliPro ES5 DP 3 3 are 110 to 240Vac versions.
 
The operation range for the 24Vdc units is 19Vdc to 29Vdc. The operation range for the 110 to 240Vac units is
77Vac to 266Vac.
 
CAUTION:
Check the voltage rating of the unit before applying control power. Control power outside of the operating
range of the power supply will damage the EntelliPro ES.
 
 
Figure 2-4 shows the EntelliPro wiring connections. Refer to Item A for power supply connections.
 
Figure 2‐4: EntelliPro ES wiring connections
 
 
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
 
CHAPTER 2: INSTALL ATION/CONFIGURATION
 
 
2.6