Electrical installation
7.3.2

24 VDC supply (X01)

The supply connection X01 is used for supplying the supply modules of the AX8000 with 24 V
voltage.
Observe the voltage tolerances for safe operation!
When connecting motors with holding brake it is essential to observe the voltage tolerances.
X01 – 24 V
voltage input on AX8620
DC
Infographic
Terminal
point
24 VDC
GND
X02 – 24 V
voltage input on AX8640
DC
Infographic
Terminal
point
24 VDC
GND
Commissioning
Commissioning of the AX8000 is only possible if the terminal points "Rbin+" and "RB -" are
bridged (delivery state) or an external brake resistor is connected to the terminal points
"R
+" and "R
-".
B
B
Without this measure the AX8000 is stopped with an error message.
42
CAUTION
Connection
24 V
±10%
DC
System and peripheral
voltage
GND
Connection
24 V
±10%
DC
System and peripheral
voltage
GND
Version: 1.6
Max. wire cross-section
2
6 mm
(AWG 8)
Max. wire cross-section
2
16 mm
(AWG 6)
Multi axis servo system AX8000
system
DC
Tightening torque
0.5 – 0.6 Nm
(4.4 – 5.3 lbf in)
Tightening torque
1.2 – 1.5 Nm