7.3.5
External and internal brake resistor
Danger to life due to high voltage on the DC link capacitors of the
servo drive AX8000!
The DC link capacitors RB+ and RB- and the test contacts DC+ and DC- on the
supply, axis and option modules can carry life-threatening voltages of ≥ 875 V
Take the following measures to avert danger:
• After disconnecting the servo drive from the mains supply, wait until the voltage has
fallen below 50 V
• Measure the voltage on the test contacts properly.
• Secure the work area properly and wear the PPE.
Connection instructions
Before you can connect the external brake resistor, you have to remove the bridge between the
contacts "RB – " and "RB
Connect the PE connection of the brake resistor with the earthing bar of the control cabinet.
X01 – brake chopper output on AX8620
Infographic
Terminal
point
R
B
R
B
X02 – brake chopper output on AX8640
Infographic
Terminal
point
R
B
R
B
Multi axis servo system AX8000
. Only then is it safe to work.
DC
+".
INT
Connection
-
Ext. brake resistor -
+
Ext. brake resistor +
Connection
-
Ext. brake resistor -
+
Ext. brake resistor +
DANGER
Max. wire cross-section
2
6 mm
(AWG 8)
Max. wire cross-section
2
16 mm
(AWG 6)
Version: 1.6
Electrical installation
.
DC
Tightening torque
0.5 – 0.6 Nm
(4.4 – 5.3 lbf in)
Tightening torque
1.2 – 1.5 Nm
(10.6 – 13.3 lbf in)
45