7.2 Interface Card

1. Disconnect cables from connectors on interface
card MK100, MK102 and MK105. If replacing
interface card, disconnect cables from connectors
MK101 and MK103
2. Remove interface card by remove 4 mounting
screws (T25) from standoffs.
Reinstall in reverse order of this procedure. Tighten T25
screws and interface card standoffs to 20 in-lbs (2.25 Nm).
Card will initialize in service mode. Follow instructions enclosed
with the spare interface card to enter data required.

7.3 Power Card

1. Remove interface card in accordance with
procedure.
2. Disconnect cables from connectors on power
card MK100, MK102, MK104, MK105, MK106,
MK107, MK109, MK110, and FK100.
3. Remove 2 interface card standoffs (8mm).
4. Remove power card by removing 4 mounting
screws (T25) and one locking stud from standoff.
5. Disconnect ground lug from ground connector.
Interface card
mounting screw
MK103
Interface card standoff
Mounting plate
FK100
7-2
VLT is a registered Danfoss trademark
MK100
MK101
MK105
MK110
FK101
FK102
MK109
MK100
Figure 7-2. Interface Card, Power Card, and Mounting Plate
6. Remove current scaling card from power card by
pushing in retaining clips on standoffs. KEEP THIS
SCALING CARD TO REINSTALL ON ANY
REPLACEMENT POWER CARD. Scaling card
controls signals operating with this specific VLT drive.
Scaling card is not part of replacement power card.
Reinstall in reverse order of this procedure. Tighten mounting
screws and interface card standoffs to 20 in-lbs (2.25 Nm).

7.4 Control Card/Power Card Mounting Plate

1. Remove control card cassette and interface card
in accordance with procedures.
2. Disconnect all cabling from power card.
3. Remove 4 mounting nuts (10mm).
4. Remove wiring from 2 fuse blocks on mounting
plate.
5. Remove optional wiring connections, as
necessary, to free mounting plate.
6. Lift plate free from chassis.
Reinstall in reverse order of this procedure. Torque 10mm
mounting nuts to 35 in-lbs (4.0 Nm).
Interface card
PCA2
MK102
Current scaling card
PCA4
Power card
PCA3
Ground connector
MK102
MK106
MK107
FK103
MK104
Locking stud
MK105
Mounting plate standoff