Technical data
10.2 Technical data, Power Modules
10.2.2

Technical data, PM240

Note
The given input currents are valid for operation without a line reactor for a line voltage of 400
V with Vk = 1 % referred to the rated power of the inverter. If a line reactor is used, the
specified values are reduced by a few percent.
General data, PM240 - IP20
Feature
Line voltage
Input frequency
Power factor λ
Starting current
Pulse frequency (factory
setting)
Electromagnetic compatibility
Braking methods
Degree of protection
Operating temperature
● without power reduction
● with power reduction
Storage temperature
Relative humidity
Environmental requirements
Shock and vibration
Electromagnetic radiation
Installation altitude
● without power reduction
● with power reduction
Standards
312
Version
3-ph. 380 V ... 480 V AC ± 10 %
The actual permissible line voltage depends on the installation altitude.
47 Hz ... 63 Hz
0,7 ... 0,85
Less than the input current
4 kHz for 0.37 kW ... 90 kW
2 kHz for 110 kW ... 250 kW
The pulse frequency can be increased in 2 kHz steps. A higher pulse frequency reduces
the permissible output current.
The devices are suitable for environmental classes C1 and C2 in conformance with
IEC61800-3. For details, see the Hardware Installation Manual, Appendix A2
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20
LO operation of all power
ratings
HO operation:
0.37 kW ... 110 kW
HO operation: 132 kW ... 200
kW
all power ratings, HO/LO
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95 % RH - condensation not permissible
Protected according to environmental class 3C2 to EN 60721-3-3 against damaging
chemical substances
Do not allow the inverter to fall and avoid it being subject to hard shocks. Do not install
the inverter in an area where it could be continuously subject to vibration.
Do not install the inverter close to sources of electromagnetic radiation.
0.37 kW ... 132 kW
up to 1000 m (3300 ft) above sea level
160 kW ... 250 kW
up to 2000 m (6500 ft) above sea level
all power ratings
up to 4000 m (13000 ft) above sea level, for details refer to the
Hardware Installation Manual.
UL, cUL, CE, C-tick, SEMI F47
In order that the system is UL-compliant, UL-certified fuses, overload circuit-breakers or
intrinsically safe motor protection devices must be used.
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
0 °C ... +40 °C (32 °F ... 104 °F)
0 °C ... +50 °C (32 °F ... 122 °F)
0 °C ... +40 °C (32 °F ... 104 °F)
up to 60 °C (140° F), for details, refer to the Hardware
Installation Manual
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD