5.5

Analog outputs

Analog output terminals
CO: rxxyy
Defining the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0
AO 1
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Figure 5-3
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
p0776[0]
p0771[0]
p0776[1]
p0771[1]
Current output (factory setting)
Voltage output
Current output
Current output (factory setting)
Voltage output
Current output
Examples for scaling characteristics
Adapting the terminal strip
Changing the function of the analog output
1. Define the analog output type using parameter
p0776 (e.g. voltage output -10 V ... 10 V or
current output 4 mA ... 20 mA).
2. Interconnect parameter p0771 with a
connector output of your choice (e.g. the
actual speed).
Connector outputs are designated with "CO" in
the parameter list of the List Manual.
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
5.5 Analog outputs
p0776[0] =
0
1
2
p0776[1] =
0
1
2
93