Transferring the setting from the memory card

If you wish to transfer the parameter setting from a memory card into the inverter
(download), you have two options:
Automatic download
The inverter power supply has been switched off.
1. Insert the memory card into the inverter.
2. Then switch-on the inverter power supply.
If there is valid parameter data on the memory card, then the inverter accepts this
automatically.
Manual download
If you do not want to switch off the power supply, then you must
transfer the parameter setting into the inverter in the following way:
1. The inverter power supply has been switched on.
2. Insert the memory card into the inverter.
STARTER
1. Go online with STARTER
2. In the expert list, set p0804 = 1.
3. Check the value of parameter p0804.
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Once data transfer has been completed, then
p0804 = 0 is automatically set.
4.6 Data backup and standard commissioning
BOP-2
1. Start data transfer in the menu "EXTRAS" -
"FROM CRD".
2. Wait until the BOP-2 signals that data transfer
has been completed.