Siemens SINAMICS G120 CU230P-2 HVAC Operating Instructions Manual page 92

Frequency converters with the control units
Hide thumbs Also See for SINAMICS G120 CU230P-2 HVAC:
Table of Contents

Advertisement

Adapting the terminal strip
5.4 Analog inputs
In addition, you must also set the switch belonging to the analog
input. You will find
• the DIP switch for AI0 and AI1 (current / voltage) on the Control
• the DIP switch for AI2 (temperature / current) on the Control Unit
If you change the analog input type using p0756, then the inverter automatically selects the
appropriate scaling of the analog input. The linear scaling characteristic is defined using two
points (p0757, p0758) and (p0759, p0760). Parameters p0757 ... p0760 are assigned to an
analog input via their index, e.g. parameters p0757[0] ... p0760[0] belong to analog input 0.
Figure 5-2
Table 5- 5
Parameter Description
p0757
p0758
p0759
p0760
p0761
90
Unit behind the lower front door.
behind the upper front door.
Examples for scaling characteristics
Parameters for the scaling characteristic and wire break monitoring
x-coordinate of 1st characteristic point [V or mA]
y coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference speed.
x-coordinate of 2nd characteristic point [V or mA]
y-coordinate of 2nd characteristic point [% of p200x]
Wire breakage monitoring response threshold
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD