Installing

3.2 Installing reactors and filters

3.2
Installing reactors and filters
Fitting inverter system components in space-saving manner
Many inverter system components are designed as base components, that is, the
component is mounted on the baseplate and the inverter mounted above it to save space.
Up to two base components can be mounted above one another.
PM240
Basic layout of a PM240 Power Module with line
reactor as base component
The line-side reactors are equipped with terminals while the reactors on the Power Module side are
equipped with a prefabricated cable. In the final installation position, the mains terminals are at the
top on frame sizes FSA to FSC, and at the bottom on frame sizes FSD to FSE.
For frame size FSA, in addition to the line reactor, a class A line filter can be used. In this case, the
mains connection is at the bottom.
Power Modules of frame size FSB and higher are available with integrated class A line filters (an
external class A line filter is not required in this case).
PM240: frame size FSA with line reactor and
output reactor or sine-wave filter
In installations containing more than two base-type system components (e.g. line filter + line reactor +
output reactor), the components must be installed to the side of the Power Module whereby the line
reactor and line filter are installed under the Power Module and the output reactor to the side.
28
Line supply
Power
Modules
Line
Line
supply
reactor
Power
Module
to the motor
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Line
reactor
PM240 Power Module frame size FSA with line
reactor and class A line filter
Output reactor
Line filter
or sine-wave
filter
Power
Module
PM240 Power Module frame size FSA with line
reactor, line filter and output reactor or sine-wave
filter
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Line
filter
Power
Modules
Line reactor
Line
supply
Line
reactor
Line supply
Output reactor
or sine-wave
filter
to the motor