Time Switch (Dtc) - Siemens SINAMICS G120 CU230P-2 HVAC Operating Instructions Manual

Frequency converters with the control units
Hide thumbs Also See for SINAMICS G120 CU230P-2 HVAC:
Table of Contents

Advertisement

7.9.8

Time switch (DTC)

The "time switch" (DTC) function, along with the real time clock in the inverter, offers the
option of controlling when signals are switched on and off.
Examples:
● Day/night switching of a temperature control
● Switching a process control from weekday to weekend.
Principle of operation of the time switch (DTC)
The inverter has three independent parameterizable time switches. Using BICO technology,
the time switch output can be interconnected with every binector of your inverter, e.g. a
digital output or a technology controller's enable signal.
Figure 7-20
Parameterizing the time switch
● Enable parameterization of the DTC: p8409 = 0.
● Parameterize the activation of the weekdays; the switching on and off times.
● Enable the setting: p8409 = 1.
Additional information is provided in the parameter list of the List Manual.
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Time behavior of the time switch using example DTC1
As long as DTC parameterization is enabled, the inverter keeps the output of all three
DTC (r84x3, x = 1, 2, 3) on LOW.
The inverter enables the DTC outputs once more.
7.9 Application-specific functions
Functions
249

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu230p-2 dpSinamics g120 cu230p-2 can

Table of Contents