Technical data
10.1 Technical data for CU230P-2
Feature
Motor temperature sensor
USB interface
Memory card (optional)
Dimensions (WxHxD)
Weight
Operating temperature
Storage temperature
Relative humidity
Open-loop/closed-loop
control procedure
The control terminals on the Control Unit are galvanically isolated from the supply voltage
(PELV).
304
Data / explanation
PTC: Short-circuit monitoring < 20 Ω, overtemperature 1650 Ω
KTY84: Short-circuit monitoring < 50 Ω, wire-break: > 2120 Ω
ThermoClick sensor with dry contact
Mini 5-pole USB
MMC card
SD card
73 mm × 199 mm × 65.5 mm
0.61 kg
0 °C ... 60 °C
0 °C ... 50 °C
- 40°C ... 70 °C%
< 95 %
V/f control for motor speeds between 0 rpm and 210000 rpm:
Linear V/f control,
Linear V/f control with FCC,
Linear V/f control with ECO mode,
Quadratic V/f control,
Multipoint V/f control,
V/f control for applications in the textile industry,
V/f control with FCC for applications in the textile industry,
V/f control with independent voltage setpoint,
Vector control for motor speeds between 0 rpm and 14400 rpm:
Speed control without encoder
Torque control without encoder
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Recommendation: 6SL3254-0AM00-0AA0
Recommendation: 6SL3254-0AM00-0AA0
For operation without operator panel
For operation with operator panel
Condensation must not be allowed to form
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD