Xantrex XPR 10-600 Operating Manual page 23

Xpr 6000 watt series programmable dc power supply
Table of Contents

Advertisement

1 Resistive Programming of Output Voltage
2 Resistive Programming of Output Current Limit
3 Selects Output Voltage Programming and Monitor Range select
4 Selects Output Current Limit Programming and Monitor Range select
5 Selects Output Voltage Control: Local or Remote
6 Selects Output Current Control: Local or Remote
7 Selects Remote Interlock Logic
8 Selects Over Temperature Shutdown Reset Mode
Figure 1.4 Programming and Monitoring S1 Switch
The rear panel at the switch is labeled with OFF at the top and ON at the bottom. Any
of the eight switches on S1 is OFF when it has been flipped up to break contact, ON
when flipped down to close contact.
Table 1.1
underlined.
Table 1.1 Rear Panel S1 Switch Assignments
Switch
Function
S1-1
1 mA current source for resistive programming of
output voltage
S1-2
1 mA current source for resistive programming of
output current limit
S1-3
Output voltage programming and monitor range
select
S1-4
Output current limit programming and monitor
range select
S1-5
Output voltage control mode select
S1-6
Output current control mode select
S1-7
Remote Interlock logic signal select
S1-8
Over temperature shutdown reset mode select
Resetting the Switches
Before making any changes to the switch settings, either turn off the AC power
switch or disable the power supply output by pushing the front panel OUT ON/OFF
switch to its IN position. This temporarily shuts down the power supply. The front
panel OFF LED turns on. Then use any small, flat-bladed screwdriver to change the
switch settings.
Release 1.1
(Switch is shown in factory default configuration.)
shows the functions assigned to each S1 switch. Factory defaults are
About The XPR Power Supply
Rear Panel Connectors and Switch
OFF
ON
Voltage source
Resistive programming
programming
(0-5 k, 0-10 k)
Voltage source
Resistive programming
programming
(0-5 k, 0-10 k)
0-5 V (0-5 k)
0-10 V (0-10 k)
0-5 V (0-5 k)
0-10 V (0-10 k)
Local Control
Remote Control
Local Control
Remote Control
Active High=OFF Active Low=OFF
Auto reset
Latch OFF
21