Hardware description
Structure > Address switch
PM - Power module
EtherNet/IP interface X1

3.2.2 Address switch

Setting the IP address
via address switch
34
For wires with a core cross-section of 0.08mm
Pos.
Function
1
---
2
DC 24V
3
0V
4
Sys DC 24V
5
---
6
DC 24V
7
0V
8
Sys 0V
I Input
EtherNet/IP interface to connect to a EtherNet/IP network. EtherNet/
IP can be operated in star topology via an already existing company
network. To operate an EtherNet/IP network at least 1 scanner
(master) is required.
The address switch serves for the configuration of the IP address. On
delivery the switch 2 (position 2) is switched to "1". Here the
EtherNet/IP coupler has the following IP address data:
n
Subnet mask: 255.255.255.0
n
IP address: 192.168.1.1
The address switch has the following assignment:
No.
Description
1
0 = DHCP off
1 = DHCP on
4. Octet (x) of the IP address 192.168.1.x
(max. value for x = 63)
2
0
2
= 1 (default switched to "1")
3
1
2
= 2
4
2
2
= 4
5
2
3
= 8
6
2
4
= 16
7
2
5
= 32
8
2
6
= 64
Type
Description
---
not connected
I
DC 24V for power section supply
I
GND for power section supply
I
DC 24V for electronic section supply
---
not connected
I
DC 24V for power section supply
I
GND for power section supply
I
GND for electronic section supply