Each module has the LEDs RUN and MF on its front side. Errors or
incorrect modules may be located by means of these LEDs.
In the following illustrations flashing LEDs are marked by ☼.
Behaviour: After PowerON the RUN LED of each module is off and
the MF LED of each module is sporadically on.
Reason: The maximum current for the electronic power supply is
exceeded.
Remedy: As soon as the sum current of the electronic power supply
is exceeded, always place the power module 007-1AB10.
Ä Chapter 2.6 'Wiring' on page 22.
Behaviour: After PowerON the MF LED of one module respectively
more modules flashes. The RUN LED remains off.
Reason: At this position a module is placed, which does not corre-
spond to the configured module.
Remedy: Match configuration and hardware structure.