3.1.4.19

SET_AUTO, 0x14

Using the SET_AUTO function, the automatic mode is switched off for the
switching channels that are described by the set bits.
The automatic mode is activated for all other switching channels.
Byte
ID
D0
D1
D2
D3
Cx
Byte
ID
D0
D1
D2
D3
Example:
For the switching channels 9, 11 and 13 the automatic mode must be switched
off ≙ (0x00002A00):
Output data: D0 = 0x00, D1 = 0x2A, D2 = 0x00, D3 = 0x00