data continuously.
Using the SET_DT function, the date and time can be set manually.
2.1.1.6.2

Configuration Data

The configuration data of the RTC module can be accessed using the
GET_CNF, GET_CNF_INC, SET_CNF and SET_CNF_INC functions. The
address offset of the relevant entry must be previously set using the
SET_ADDR function. When the data is accessed via the GET_CNF_INC or
SET_CNF_INC functions, the address offset is automatically increased by 4
bytes after the read or write operation is complete. For a write access with
SET_CNF and SET_CNF_INC, the valid password must previously be
entered at address offset 0x0310.
The configuration data is structured as follows:
Offset
0x0000 T0
0x0018 T1
0x0030 T2
0x02E8 T31
0x0300 Auto
0x0308 TimeZone
0x030C DstBias
0x0310 Password
0x0314 Init
0x031C Antenna
2.1.1.6.2.1
Timer Configuration (T0 ... T31)
The module has a timer function with 32 switching points and 32 output
channels. Any of the 32 channels can be switched on or off at each switching
point. All switching points are cyclically recurrent. The actual status of the
switching channels can be queried via the GET_CHANNEL function and can
be changed manually via the SET_CHANNEL and CLEAR_CHANNEL
functions.
WAGO-I/O-SYSTEM 750
I/O-Modules
Function
Description
Configuration Timer 0
Configuration Timer 1
Configuration Timer 2
...
...
...
Configuration Timer 31
Auto/manual for each channel (0 = auto)
Offset for time zone (seconds)
Offset for summer time (daylight saving time, seconds)
0x3EA8D0F1
0x1F0D8AE3
Selection of the time signal transmitter
750-640 [RTC Module]
Functional Description
• 13
Length
24
24
24
...
24
4
4
4
4
4
4