Clear_Channel, 0X12 - WAGO 750-640 Manual

Fieldbus independent i/o modules, rtc module
Table of Contents

Advertisement

3.1.4.17

CLEAR_CHANNEL, 0x12

Using the CLEAR_CHANNEL function, the switching states of the switching
channels that are described by the set bits are set to zero.
In automatic mode, the switching states will be overwritten at the next alarm
event if necessary.
Byte
ID
D0
D1
D2
D3
Cx
Byte
ID
D0
D1
D2
D3
Example:
Switching channels 17, 19, 21 and 23 must be set ≙ (0x00AA0000):
Output data: D0 = 0x00, D1 = 0x00, D2 = 0xAA, D3 = 0x00
WAGO-I/O-SYSTEM 750
I/O-Modules
Function Request
7
6
5
2
2
2
C
0
0
0
C7
C6
C5
C15
C14
C13
C23
C22
C21
C31
C30
C29
Switching channel 0 – switching channel 31
Function Response
7
6
5
2
2
2
S
0
0
0
4
3
2
1
2
2
2
2
0
0
0
0
0x12
C4
C3
C2
C1
C12
C11
C10
C9
C20
C19
C18
C17
C28
C27
C26
C25
4
3
2
1
2
2
2
2
0
0
0
0
0x12
0x00
0x00
0x00
0x00
Attachment
Functions
0
2
TR
C0
C8
C16
C24
0
2
TA
• 49

Advertisement

Table of Contents
loading

Table of Contents