Setting the timers is done as follows:
Timer Start
1
2
3
4
The hexadecimal values are as follows:
Timer Start
1
2
3
4
2.1.1.6.2.2

Auto

The automatic mode of the relevant switching channel is switched off for each
bit set in Auto. The switching channel can only be changed using the
SET_CHANNEL and CLEAR_CHANNEL functions.
2.1.1.6.2.3

TimeZone

Time zone. For CET applies e.g. +1h = 3600s $ = 0x00000E10.
2.1.1.6.2.4

DstBias

For the transition from winter time to summer time, the content of DstBias
(Daylight Saving Time) is added to the TimeZone when the time is being
evaluated. This way, the transition can be performed without having to change
the time or time zone.
2.1.1.6.2.5

Password

Access to the configuration data is protected by means of a password.
Therefore, only write access is possible if 0x3EA8D0F1 has been entered.
2.1.1.6.2.6

Init

When 0x1F0D8AE3 is written to Init, all configuration data is overwritten
with zero.
WAGO-I/O-SYSTEM 750
I/O-Modules
Stop
01.01.1970
-
06:00:00
01.01.1970
-
18:00:00
26.05.2003
13.06.2003
06:00:01
06:00:01
01.01.1970
-
19:30:00
Stop
0x00005460
0x00000000
0x0000FD20
0x00000000
0x3ED1AD61
0x3EE96861
0x00011238
0x00000000
750-640 [RTC Module]
Functional Description
Interval
On
24h
Channel 1
24h
-
24h
-
24h
-
Interval
On
0x00015180
0x00000001
0x00015180
0x00000000
0x00015180
0x00000000
0x00015180
0x00000000
• 15
Off
Days
-
Mo-Fr
Channel 1
Every
Channel 1
Every
Channel 4
Every
Off
Days
0x00000000
0x1F
0x00000001
0x00
0x00000001
0x00
0x00000008
0x00