Antenna; Service Data - WAGO 750-640 Manual

Fieldbus independent i/o modules, rtc module
Table of Contents

Advertisement

16 •
750-640 [RTC Module]
Functional Description
2.1.1.6.2.7

Antenna

This is how to select the decoder scheme for time signal reception.
Byte
0
0
Note on setting the time zone and summer time using different antennas:
• The DCF77 transmitter sends CET (Central European Time) or CEST
• The WWVB transmitter sends in UTC. If the module is operated at the US
2.1.1.6.3

Service Data

Getting or setting the "up to now accumulated run time and maintenance
interval" is done using the GET_OPH, GET_OPH_INC, SET_OPH and
SET_OPH_INC functions for each channel. The address offset of the relevant
hours-run meter must previously be set using the SET_ADDR function. When
the data is accessed via the GET_CNF_INC or SET_CNF_INC functions, the
address offset is automatically increased by 4 bytes after the read or write
operation is complete. For a write access with SET_CNF and SET_CNF_INC,
the valid password must previously be entered at address offset 0x0310 .
The hours-run meter is stopped in the event of a power failure independent of
the status of the relevant channel.
Offset
0x0000 Hours-run meter channel 0
0x0008 Hours-run meter channel 1
0x0010 Hours-run meter channel 2
0x00F8 Hours-run meter channel 31
Bit
Function
0 ... 1
0: No time signal reception
1: DCF77 Decoder activated
2: WWVB Decoder activated
2
DCF77 Polarity reversed
0 = Low-active
1 = High-active
(Central European Summer Time), the summer time setting (DstBias)
remains set to zero. The time zone for Germany is 0.
east coast (Eastern Time) for example, an offset of 5 hours (0xFFFFB9B0)
must be entered in the TimeZone. The transition from winter time to
summer time is done using a status bit within the time telegram. By setting
this bit, one more hour will be transmitted by the module. Within the
module, the transition is always performed at 00:00.
Function
...
...
Length
8
8
8
...
8
WAGO-I/O-SYSTEM 750
I/O-Modules