Application Examples
SLC Application Example
One sequence 1:
Start – ramp up – run at reference speed 2 sec – ramp down and hold shaft until stop.
Set the ramping times in par. 3-41 and 3-42 to the wanted times
(
. 1 − 25 )
t
n
par
×
acc
norm
t
=
ramp
ref
RPM
Set term 27 to No Operation (par. 5-12)
Set Preset reference 0 to first preset speed (par. 3-10 [0]) in percentage of Max reference speed (par.
3-03). Ex.: 60%
Set preset reference 1 to second preset speed (par. 3-10 [1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in par. 13-20 [0]. Ex.: 2 sec.
Set Event 1 in par. 13-51 [1] to True [1]
Set Event 2 in par. 13-51 [2] to On Reference [4]
Set Event 3 in par. 13-51 [3] to Time Out 0 [30]
Set Event 4 in par. 13-51 [1] to False [0]
Set Action 1 in par. 13-52 [1] to Select preset 0 [10]
Set Action 2 in par. 13-52 [2] to Start Timer 0 [29]
Set Action 3 in par. 13-52 [3] to Select preset 1 [11]
Set Action 4 in par. 13-52 [4] to No Action [1]