FC 300 Design Guide
ALARM/WARNING 28
Brake check failed:
Brake resistor fault: the brake resistor is not con-
nected/working.
ALARM 29
Drive over temperature:
If the enclosure is IP 20 or IP 21/Type 1, the cut-
out temperature of the heat-sink is 95
The temperature fault cannot be reset, until the
temperature of the heatsink is below 70
The fault could be:
-
Ambient temperature too high
-
Too long motor cable
ALARM 30
Motor phase U missing:
Motor phase U between the frequency converter
and the the motor is missing.
Turn off the frequency converter and check motor
phase U.
ALARM 31
Motor phase V missing:
Motor phase V between the frequency converter
and the motor is missing.
Turn off the frequency converter and check motor
phase V.
ALARM 32
Motor phase W missing:
Motor phase W between the frequency converter
and the motor is missing.
Turn off the frequency converter and check motor
phase W.
ALARM 33

Inrush fault:

Too many powerups have occured within a short
time period. See the chapter General Specifica-
tions for the allowed number of powerups within
one minute.
WARNING/ALARM 34

Fieldbus communication fault:

The fieldbus on the communication option card is
not working.
WARNING/ALARM 36
Mains failure:
This warning/alarm is only active if the supply
voltage to the frequency converter is lost and pa-
rameter 14-10 is NOT set to OFF. Possible correc-
tion: check the fuses to the frequency converter
Troubleshooting
ALARM 38
Internal fault:
By this alarm it may be necessary to contact your
Danfoss supplier. Some typical alarm messages:
o
C +5
o
C.
o
C +5
o
C.
®
MG.33.B8.02 - VLT
is a registered Danfoss trademark
0 The serial port cannot be initialized. Se-
rious hardware failure
256 The power EEPROM data is defect or too
old
512 The control board EEPROM data is defect
or too old
513 Communication time out Reading EE-
PROM data
514 Communication time out Reading EE-
PROM data
515 The Application Orientated Control can-
not recognize the EEPROM data
516 Cannot write write to the EEPROM be-
cause a write command is on progress
517 The write command is under time out
518 Failure in the EEPROM
519 Missing or invalid BarCode data in EE-
PROM 1024 – 1279 CAN telegram cannot
be sent. (1027 indicate a possible hard-
ware failure)
1281 Digital Signal Processor flash time-out
1282 Power micro software version mismatch
1283 Power EEPROM data version mismatch
1284 Cannot read Digital Signal Processor
software version
1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
1301 Option SW in slot C0 is too old
1302 Option SW in slot C1 is too old
1315 Option SW in slot A is not supported (not
allowed)
1316 Option SW in slot B is not supported (not
allowed)
1317 Option SW in slot C0 is not supported
(not allowed)
1318 Option SW in slot C1 is not supported
(not allowed)
1536 An exception in the Application Orienta-
ted Control is registered. Debug infor-
mation written in LCP
1792 DSP watchdog is active. Debugging of
power part data Motor Orientated Con-
trol data not transferred correctly
2049 Power data restarted
2315 Missing SW version from power unit
2816 Stack overflow Control board module
2817 Scheduler slow tasks