5.5.3.8

X46 terminal strip

Table 5- 49
Max. connectable cross-section: 1.5 mm
The terminal strip is coded at terminal 1; please use the corresponding connector from the accessory
pack.
Note
The interface is provided with the Motor Module for connecting the Safe Brake Adapter.
5.5.3.9

X47 contactor feedback signal

Table 5- 50
Max. connectable cross-section: 1.5 mm
The terminal strip is coded at terminal 3; please use the corresponding connector from the accessory
pack.
The monitoring of the precharging and main contactors of the Active Line Module Chassis-2
is activated in the factory settings.
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
Terminal strip X46
Connector
Terminal
1
2
3
4
5
6
Terminal strip X47, contactor feedback signal
Connector
Terminal
1
2
3
4
5
6
Function
Technical specifications
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
2
Signal name
Technical specifications
VL_R
Precharging contactor feedback signal
Supply voltage: 24 V DC
M
Max. Load current: 10 mA
HS_R
Main contactor feedback signal
Supply voltage: 24 V DC
M
Max. Load current: 10 mA
NC
Reserved, do not use
NC
Reserved, do not use
2
Line Modules
5.5 Active Line Modules Chassis-2
233