Siemens SINAMICS S120 Equipment Manual page 149

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

For a version with one precharging resistor for each phase, a Sirius 3RT2027 is
recommended.
For a version with two precharging resistors connected in parallel for each phase, a Sirius
3RT2037 contactor is recommended.
Precharging resistors
The precharging resistors are used to limit the current while precharging.
Table 5- 12
Technical data for the precharging resistors
Category
Rated voltage
Frequency
Resistance value
Pulse energy
1)
Precharging current
2)
- one resistor per phase
- two resistors per phase in parallel
Ambient temperature
Article number
The pulse energy may only occur every 3 minutes
1)
Line current present at the start of the precharging (initial rms value)
2)
As the precharging resistors can get hot, sufficient cooling and clearance to adjacent
components must be ensured in operation.
Fuses
The pre-charging input circuit components are protected against overload using fuses.
In a version with one precharging resistor for each phase, fuses of the 3NE1 817-0 (50 A)
type are recommended.
For a version with two precharging resistors connected in parallel for each phase, 3NE1 021-
0 fuses (100 A) are recommended.
Circuit breaker
The circuit breaker is used to connect the Basic Line Module to the line supply.
A 3WL1220 circuit breaker is recommended.
The circuit breaker is controlled via terminal -X9: 3, 4 of the Basic Line Module.
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
Unit
3 AC 380 ... 480 V
V
690 VAC
Hz
47 ... 63
Ω
2.2 ±10%
Ws
18000
A
91
A
182
° C
60
6SL3000-0KE12-2AA0
Line Modules
5.2 Basic Line Modules
3 AC 500 ... 690 V
690 VAC
47 ... 63
4.0 ±10%
18000
86
172
60
6SL3000-0KH14-0AA0
147

Advertisement

Table of Contents
loading

Table of Contents