Line Modules
5.3 Smart Line Modules
Article number
Dimensions
- Width
- Height
- Depth
Frame size
Weight, approx.
Recommended fuse
2)
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
2)
Minimum current required for reliable triggering of the protective devices.
3)
184
6SL3330– 6TE41–7AA3
mm
mm
mm
kg
kA
3)
704
1480
550
JX
458
3NE1448-2
2
850
3
21
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9