Line-side power components
4.7 Active Interface Modules Chassis-2
NOTICE
Damage to the device through not removing the connection clip with a non-grounded line
supply
Failure to remove the connection clip to the basic interference suppression module on an
ungrounded line supply (IT system) can cause significant damage to the device.
• With a non-grounded line supply (IT system), remove the connection clip to the basic
Removing the connector jumper on the VSM10 Voltage Sensing Module
When operating the Active Interface Module Chassis-2 on a non-grounded line supply (IT
system), at the Voltage Sensing Module (VSM10), remove the plug-in jumper in terminal
X530 at the lower side of the component.
Use two screwdrivers or another suitable tool to relieve the holding springs in the terminal
and then withdraw the plug-in jumper.
Terminal X530 with connector jumper
118
interference suppression module.
Relieve the springs and withdraw the connector
jumper