X609 Terminal Strip; X1 Temperature Sensor Connection At The Filter Reactor - Siemens SINAMICS S120 Equipment Manual

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
3.2 Active Interface Modules
3.2.3.6

X609 terminal strip

Table 3- 8
Terminal strip X609
Terminal
PE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
PE
Max. connectable cross-section: 2.5 mm
3.2.3.7

X1 temperature sensor connection at the filter reactor

Table 3- 9
Terminal
1
2
Max. connectable cross-section: 2.5 mm
Note
When operating the Active Interface Module, it is not necessary to evaluate the temperature
sensor at the filter reactor.
In the filter module cooling circuit, a water-cooled resistor has an integrated PT1000
temperature sensor, which is internally evaluated by the VSM10.
The following temperature thresholds apply for additional filter reactor temperature
monitoring:
● Alarm: 140 °C
● Fault: 150 °C
52
Designation
PE
P24
P24
M
M
L
L
N
N
Pre-charging contactor–A1
Pre-charging contactor–A2
Bypass contactor–A1
Bypass contactor–A2
Contactor feedback signal 1
Contactor feedback signal 2
PE
2
Terminal strip X1 at filter reactor
Designations
PT1000 temperature sensor connection
Technical data
PE connection
External 24 V DC supply
Voltage: 24 V DC (20.4 ... 28.5 V)
Current consumption: max. 0.25 A
Voltage: 230 V AC (195.5 ... 264.5 V)
Current consumption: max. 4 A
Voltage: 230 V AC (195.5 ...
264.5 V)
Current consumption: max. 4 A
Voltage: 230 V AC (195.5 ...
264.5 V)
Current consumption: max. 6 A
Voltage: 230 V AC (195.5 ... 264.5 V)

 M ax. permissible current: 6 A
PE connection
2
Water-cooled chassis power units for common cooling circuits
To Active Line Module, X9:5
To Active Line Module, X9:6
To Active Line Module, X9:3
To Active Line Module, X9:4
Manual, 08/2017, 6SL3097-4AM10-0BP0

Advertisement

Table of Contents
loading

Table of Contents