Active Interface Modules Chassis-2; Description - Siemens SINAMICS S120 Equipment Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.7

Active Interface Modules Chassis-2

4.7.1

Description

Active Interface Modules Chassis-2 are used in conjunction with the Active Line Modules
Chassis-2. The Active Interface Modules Chassis-2 contain a Clean Power Filter with basic
RI suppression, line voltage sensing circuit and monitoring sensors.
The pre-charging input circuit that is necessary for operation, comprised of resistors, a pre-
charge contactor and a main contactor, must be provided separately. The pre-charge
contactor is activated from the Active Line Module Chassis-2.
The vast majority of line harmonics are suppressed by the Clean Power Filter.
The Active Interface Module contains:
● Clean Power Filter
● Line reactor
● Voltage Sensing Module VSM10
● Fan
Figure 4-26
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
Active Interface Module Chassis-2
Line-side power components
4.7 Active Interface Modules Chassis-2
103

Advertisement

Table of Contents
loading

Table of Contents