Line Modules
5.4 Active Line Modules
5.4.6.3
Overload capability
The Active Line Modules have an overload reserve.
The criterion for overload is that the Active Line Module is operated as a maximum with its
base load current before and after the overload occurs (a load duration of 300 s is used as a
basis here).
High overload
The base load current for a high overload I
max. current I
Figure 5-39
218
can flow for 5 s.
max_DC
High overload
is based on a duty cycle of 150% for 60 s; the
H_DC
Manual, 07/2019, 6SL3097-4AE00-0BP9
Air-cooled chassis power units