Cabinet design and EMC
10.3 Cabinet air conditioning
Table 10- 5
Volume flow rate, opening cross-sections
Article number
6SL3300-
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet inlet
[m²]
outlet
[m²]
Article number
6SL3301-
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet inlet
[m²]
outlet
[m²]
Article number
6SL3330-
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet inlet
[m²]
outlet
[m²]
Article number
6SL3330-
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet inlet
[m²]
outlet
[m²]
424
Active Interface Modules
7TE32-6AA0
7TE33-8AA0
7TE35-0AA0
0.24
0.47
0.1
0.25
0.1
0.25
Active Interface Modules Chassis-2
Basic Line Modules
1TE34-2AA3
1TE41-2AA3
1TE35-3AA3
1TE41-5AA3
1TE38-2AA3
1TE41-6AA3
1TG33-0AA3
1TG41-1AA3
1TG34-3AA3
1TG41-4AA3
1TG36-8AA3
1TG41-8AA3
0.17
0.36
0.1
0.19
0.1
0.19
Smart Line Modules
6TE35-5AA3
6TE41-1AA3
6TE37-3AA3
6TG38-8AA3
6TG35-5AA3
0.36
0.78
0.19
0.28
0.19
0.28
7TE38-4AA0
7TE41-4AA0
7TG35-8AA0
7TG37-4AA0
7TG41-3AA0
0.4
0.2
0.2
7TE36-4AA0
7TE41-0AA0
0.61
0.38
0.28
6TE41-3AA3
6TE41-7AA3
6TG41-2AA3
6TG41-7AA3
1.08
0.38
0.38
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9