Siemens SINAMICS S120 Equipment Manual page 399

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cable cross-sections
In a dV/dt filter with separate voltage peak limiter (type 4), the connections between dV/dt
reactor and voltage peak limiter are already installed on the voltage peak limiter.
Table 9- 36
dV/dt filter compact plus volt-
Table 9- 37
Cable type: 600 V, UL style 3271, operating temperature 125° C
Fire and device damage as a result of ground fault/short-circuit
Inadequate installation of the cables to the Motor Module DC link can result in a ground
fault/short-circuit and place persons at risk as a result of the associated smoke and fire.
• Comply with local installation regulations that enable this fault to be ruled out.
• Protect the cables from mechanical damage.
• In addition, apply one of the following measures:
NOTICE
Damage to the dV/dt filter compact due to mechanical load on connections
The connections at the dV/dt filter compact are not designed for direct mechanical
connection to the motor cables.
• Take measures on the plant or system side to ensure that the connections cannot be
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
Cable cross-sections for connections between a dV/dt filter and Motor Module
age peak limiter
Type 1
Type 2
Type 3
Type 4
Connection cable enclosed for connecting dV/dt reactor and voltage peak limiter
Voltage peak limiter
Type 4
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
deformed by the mechanical load exerted by the connected cables.
9.4 dv/dt filter compact plus Voltage Peak Limiter
Cross-section
[mm²]
16
25
50
95
Cross-section
Lug for connecting 1U2 / 1V2 / 1W2 on the dV/dt
[mm²]
70
Motor-side power components
Connection on dV/dt filter
Screw M8 / 12 Nm
Screw M8 / 12 Nm
Copper bar for M8 bolt / 12 Nm
Copper bar for M8 bolt / 12 Nm
reactor
M12
397