SOFTWARE SHUTDOWN

Running the software shutdown procedure causes the following:
1) Reset of Autotuning, Selftuning and Softstart.
2) Digital input (if present) enabled only if assigned to SW shutdown function.
3) In case of switch-on after SW shutdown, any ramp for the set (set gradient) starts from the PV.
4) Outputs OFF: except for rL.4 and rL.6 which are forced ON.
5) Reset of HB alarm.
6) Reset of LBA alarm.
7) The Heat and Cool bit on the state word STATUS_STRUMENTO and POWER are reset.
8) At shutdown, the current power is saved. At switch-on, integral power is recalculated as the difference between saved power
and proportional power; this calculation is defined as "desaturation at switch-on."
9) The state of alarms (AL1...AL4, ALHBTA1...ALHBTA3) is reset.
140
diG.
618
diG. 2
11
SOFTWARE LAUNCH/
SHUTDOWN
bit
700
OFF. T
Read state
68
STATE of DIGITAL
INPUT 1
bit
92
STATE of DIGITAL
INPUT 2
bit
305
52
R/W
Digital input function
Digital input 2 function
R/W
OFF = On
R/W
ON =Off
R/W
Modes at software shutdown
OFF = Digital input 1 off
R
ON = Digital input 1 on
OFF = Digital input 2 off
R
ON = Digital input 2 on
R/W
Instrument state
See: Table of digital input functions
Table of software shutdown methods
0
Outputs rL.1- rL.2 - rL.3 - rL.5 = OFF
Outputs rL.4 - rL.6 = ON
Alarms AL.1 -AL.2 -AL.3 - AL.4 disabled
1
Outputs rL.1- rL.2 - rL.3 - rL.5 = OFF
Outputs rL.4 - rL.6 = ON
Alarms AL.1 -AL.2 -AL.3 - AL.4 enabled
+16
Restart of the Softstart at the switch-on software (ON Software)
See: Table of instrument settings
880397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
0
0
0
0