Hw/Sw Information - gefran GFX4 Configuration And Programming Manual

4-zone modular power controller
Hide thumbs Also See for GFX4:
Table of Contents

Advertisement

The following data registers can be used to identify the controller HW/SW and check its operation.
122
UPD
85
Err
606
Er. 2
190
(. x d
(*) In correspondence to the SV value on the GFX-OP display, the digits indicate bit
values as follows:
- THOUSANDS and HUNDREDS
(Power GFX4 / GFXTERMO4) correspond to bits 6 to 9
- TENS (COOL outputs) correspond to bits 1 to 4
- ONES (Number of CT) correspond to bits 10 to 14
508
(. x d1
(*) In correspondence to the SV value on the GFX-OP display, the digits indicate bit
values as follows:
- TENS (auxiliary inputs) correspond to bits 0 to 1
- ONES (fieldbus interface) correspond to bits 6 to 15
693
Upd. F
697
695
(oD. F
696
bAu. F
60

HW/SW INFORMATION

R
Software version code
Self-diagnosis
R
error code for main input
Self-diagnosis
R
error code for auxiliary input
R
Hardware configuration codes
R
Hardware configuration codes 1
R
Fieldbus software version
R
Fieldbus node
R
Fieldbus baudrate
Table of main input errors
0
No Error
1
Lo (process variable value < Lo.S)
2
Hi (process variable value > Hi.S)
3
ERR [third wire interrupted for PT100 or input values below minimum
limits (ex. for TC with connection error)]
4
SBR (probe interrupted or input values beyond maximum limits)
Table of hardware configuration codes
bit
0
= 1 OUTPUT COOL absent
1
= 1 OUTPUT COOL relay
2
= 1 OUTPUT COOL logic
3
= 1 OUTPUT COOL continuous 0...20mA / 0...10V
4
= 1 OUTPUT COOL triac 250Vac 1A
5
-
6
= 1 GFX4 absent (GFXTERMO4 present)
7
= 1 GFX4 30 kW
8
= 1 GFX4 60 kW
9
= 1 GFX4 80 kW
10
= 1 GFX4 without TA
11
= 1 GFX4 with 1 TA
12
= 1 GFX4 with 4TA
13
= 1 GFXTERMO4 without TA
14
= 1 GFXTERMO4 with 4TA
Table of hardware configuration codes1
bit
0
= 1 INPUT AUX absent
1
= 1 INPUT AUX TC / 60mV
2
-
3
= 1 FIELDBUS ETH4 (ProfiNET)
4
= 1 FIELDBUS ETH5
5
= 1 FIELDBUS ETH6
6
= 1 FIELDBUS absent
7
= 1 FIELDBUS Modbus
8
= 1 FIELDBUS Profibus
9
= 1 FIELDBUS CanOpen
10
= 1 FIELDBUS DeviceNet
11
= 1 FIELDBUS Ethernet
12
= 1 FIELDBUS Euromap66
13
= 1 FIELDBUS Eth3
14
= 1 FIELDBUS Eth2 (EtherCAT)
15
= 1 FIELDBUS Eth1 (Ethernet IP)
Profibus
0
12.00 Mbit/s
0
1
6.00 Mbit/s
1
2
3.00 Mbit/s
2
3
1.50 Mbit/s
3
4
500.00 Kbit/s
4
5
187.50 Kbit/s
5
6
93.75 Kbit/s
6
7
45.45 Kbit/s
7
8
19.20 Kbit/s
8
9
9.60 Kbit/s
880397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
Value indicated
by GFX-OP (*)
0
r
d
t
c
te
30
60
80
0
1
4
0
4
Value indicated
by GFX-OP (*)
0
1
O
m
P
C
d
E
c
3
2
1
Canopen
Devicenet
1000 Kbit/s
0
125 Kbit/s
800 Kbit/s
1
250 Kbit/s
500 Kbit/s
2
500 Kbit/s
250 Kbit/s
125 Kbit/s
Ethernet
100 Kbit/s
0
100 Mbit/s
50 Kbit/s
1
10 Mbit/s
20 Kbit/s
10 Kbit/s