gefran GFX4 Configuration And Programming Manual page 20

4-zone modular power controller
Hide thumbs Also See for GFX4:
Table of Contents

Advertisement

Read state
602
In. 2
606
Er. 2
ADVANCED SETTINGS
Input filter
604
FLt. 2
Sets a low pass filter on the auxiliary input, running the average of values read in the
specified time interval. If = 0 , excludes the average filter on sampled values.
FUNCTIONAL DIAGRAM
Auxiliary
input
20
R
Value of auxiliary input
Error code for self-diagnosis
R
of auxiliary input
R/W
Digital filter for auxiliary input
Select sensor
(AI.2)
0
No error
1
Lo (value of process variable is < Lo.S)
2
Hi (value of process variable is > Hi.S)
3
ERR [third wire interrupted for PT100 or input values below minimum
limits (ex.: for TC with connection error)]
4
SBR (probe interrupted or input values beyond maximum limits)
0.0 ... 20.0 sec
Scale limits, decimal
point, Offset (H.S2,
L.S2, dP.2 or FS.2)
880397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
Error code table
Internal
variable In.2
Low pass f
ilter
(Flt.2)
0.1
See generic
alarms and
Control

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfxtermo4