ALARM SBR - ERR

This alarm is always ON and cannot be deactivated. It controls correct functioning of the probe connected to the main
input.
In case of broken probe:
- the state of alarms AL1, AL2, AL3 and AL4 is set based on the value of parameter rEL;
- control power control is set to the value of parameter FAP.
Identification of the type of break detected on the main input is contained in Err.
Enable alarm
229
rEL
228
fa. p
Read state
85
Err
9
STATE OF INPUT
IN SBR
bit
FUNCTIONAL DIAGRAM
Power control
(PID output)
Manual power
Manual
power/remote
(auxiliary analog input)
Power limit for Fault
Action (FA.P)
Power limit for LBA
alarm (Lb.P)
Average power for
power alarm
32

(probe in short or connection error)

R/W
Fault action
(definition of state in case
of broken probe)
Sbr, Err
Only for main input
Fault action power
R/W
(supplied in conditions of broken probe)
Error code in self-diagnostics
R
of main input
OFF = -
R
ON = Input in SBR
Auxiliary
analog input
function
(tP.2)
Table of probe alarm settings
Alarm
Alarm
1
2
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
OFF
OFF
5
ON
OFF
6
OFF
ON
7
ON
ON
8
OFF
OFF
9
ON
OFF
10
OFF
ON
11
ON
ON
12
OFF
OFF
13
ON
OFF
14
OFF
ON
15
ON
ON
see: HOT RUNNERS CONTROLI
-100,0 ..100,0 %
See: Table of error codes
Power
control.
Output
Select LOC /
power
REM (D1G.,
d1G.2)
880397M_MSW_GFX4-GFXTERMO4_08-2018_ENG
Alarm
Alarm
3
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
State of variable Ou.P
See outputs
limit
0
0,0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfxtermo4

Table of Contents