[50GSOTF.3I0_Set] is the current setting of the zero sequence SOTF overcurrent protection;
"t
" is the setting [50GSOTF.t_Op], the time setting of the zero sequence SOTF
SOTFROC
overcurrent protection;
[50GSOTF.En] is the logic setting of the zero sequence SOTF overcurrent protection;
[50GSOTF.En1] is the binary signal for enabling the zero sequence SOTF overcurrent
protection;
[50GSOTF.Blk] is the binary signal for blocking the zero sequence SOTF overcurrent
protection;
[SOTF.Opt_Mode] is the setting for selecting the acceleration mode of the SOTF protection;
"t
" is the setting [SOTF.t_En], the enabling time setting of the SOTF protection;
EnSOTF
[79.Ready] is used to denote the auto-recloser is ready for operating;
[79.Close_3PSx] (x:1~4) means that the auto-recloser operates;
"SOTF.ManClsCB" denotes the circuit breaker is closed manually (local or remote), f or
example, the circuit breaker is closed by the remote closing command from the SAS or
SCADA, or by pressing the closing button on the control panel.

3.10.2 SOTF Protection Settings

All the settings of the SOTF protection are listed in the following table. For the information about
the common explanation of the settings, see Section 7.3.
No.
Menu text
1
SOTF.t_En
2
SOTF.Opt_ Mode
3
50PSOTF.I_Set
4
50PSOTF.t_Op
5
50PSOTF.En
6
50PSOTF.OutMap
7
50GSOTF.3I0_Set
8
50GSOTF.t_Op
9
50GSOTF.En
10
50GSOTF.OutMap
PCS-9611 Feeder Relay
Explanation
The enabling time setting of the SOTF protection
The setting for s electing the acceleration tripping
mode of the SOTF protection
The current s etting of the SOTF o vercurrent
protection
The time setting of the SOTF overcurrent
protection
The logic s etting of the SOTF o vercurrent
protection
The output matrix setting of the SOTF o vercurrent
protection
The current setting of the zero sequence SOTF
overcurrent protection
The time s etting of the zero sequence SOTF
overcurrent protection
The logic setting of the zero sequence SOTF
overcurrent protection
The output matrix setting of the zero sequence
SOTF o vercurrent protection
Date: 2014-04-08
3 Operation Theory
Range
Step
0~100s
0.001s
0~1
1
0.05In~30In
0.001A
0~100s
0.001s
0~1
1
0x00000 ~
1
0xFFFFF
0.05In~30In
0.001A
0~100s
0.001s
0~1
1
0x00000 ~
1
0xFFFFF
3-39