7 Settings
No.
Menu text
1
DCAO.Opt_ Type_1
2
DCAO.Opt_ Type_2
3
DCAO.Opt_ Type_3
4
DCAO.Opt_ Type_4
5
DCAO.Ma x_1
6
DCAO.Ma x_2
7
DCAO.Ma x_3
8
DCAO.Ma x_4
NOTE!
The setting [DCAO.Opt_Type_x] (x: 1~4) is used to select the type of the analog output: "0" is
1.
4~20mA, and "1" is 0~10V.
7.5 Logic Link Settings
The logic link settings (in the submenu "Logic Links") are used to determine whether the relevant
function of this relay is enabled or disabled. If this relay supports the logic link function, it will have
a corresponding submenu in the submenu "Logic Links" for the logic link settings.
7.5.1 Function Link Settings
The function link settings (in the submenu "Function Links") are used to determine whether the
relevant functional elements are enabled or disabled.
7.5.2 GOOSE Link Settings
The GOOSE link settings (in the submenu "GOOSE Links") are used to determine whether the
relevant GOOSE elements are enabled or disabled. The GOOSE Link Settings in this relay which
are configured according to a practical engineering should be taken as final and binding.
7.5.3 Spare Link Settings
The spare link settings (in the submenu "Spare Links") are used for future application. It can be
defined as one of above three link settings through the PCS-Explorer configuration tool.
7.6 Device Related Settings
The device related settings (in the submenu "Device Setup") are used for setting the operation
parameters and communication parameters of this device.
7-30
Explanation
The type of the No.1 channel of DC analog output
The type of the No.2 channel of DC analog output
The type of the No.3 channel of DC analog output
The type of the No.4 channel of DC analog output
The value relates to the maximum value (20mA or
10V) of the No.1 channel of DC analog output
The value relates to the maximum value (20mA or
10V) of the No.2 channel of DC analog output
The value relates to the maximum value (20mA or
10V) of the No.3 channel of DC analog output
The value relates to the maximum value (20mA or
10V) of the No.4 channel of DC analog output
Date: 2014-04-08
Range
Step
0~1
1
0~1
1
0~1
1
0~1
1
0.5~1000.0
0.001
0.5~1000.0
0.001
0.5~1000.0
0.001
0.5~1000.0
0.001
PCS-9611 Feeder Relay