2 Technical Data
2.1.4.5 Ethernet Port for Debugging
Medium
Electrical Ethernet
(in front panel)
2.1.4.6 Process Level Interface
Medium
Optical Ethernet

2.1.5 Type Test

2.1.5.1 Environmental Tests
Dry cold test
Dry heat test
Damp heat test
Cyclic temperature with
humidity test
2.1.5.2 Electrical Tests
Dielectric test
Impulse voltage test
Overvoltage category
Insulation measurement
Pollution degree
2.1.5.3 Electromagnetic Compatibility
1MHz burst disturbance tests
- Common mode
- Differential mode
Electrostatic discharge tests
- For contact discharge
- For air discharge
2-4
Port number
Connector type
Transmission rate
Transmission standard
Transmission distance
Safety le vel
Optical fiber material
Optical fiber type
Connector type
Wavelength
Transmission dis tance
Minimum transmission power
Reception sensitivity
IEC60068-2-1: 2007, 16h at -25° C
IEC60068-2-2: 2007, 16h at +55° C
IEC60068-2-78: 2001, 10 days, 93%RH, +55° C
IEC60068-2-30: 2005, six (12+12hours) cycles, 95%RH,
low temperature +25° C, high temperature +55° C
IEC60255-27: 2005, test voltage: 2kV, 50Hz, 1min
IEC60255-5: 2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs,
source energy 0.5J
IEC60255-5: 2000, Class III
IEC60255-5: 2000, insulation resistance >100MΩ @ 500Vdc
IEC60225-1: 2009, Class II
IEC60255-22-1: 2007, Class III
IEC60255-22-2: 2008, Class IV
Date: 2014-04-08
Parameters
1
RJ-45
100Mbits/s
100Base-TX
< 100m
Isolation to ELV level
Parameters
Glass fiber
Multi-mode
LC
1310nm
< 2000m
-20dBm
-30dBm
2.5kV
1.0kV
8.0kV
15.0kV
ST
820nm
PCS-9611 Feeder Relay