Current Transformer Requirements - NR Electric PCS-9611 Instruction Manual

Feeder relay
Hide thumbs Also See for PCS-9611:
Table of Contents

Advertisement

6 Hardware
(5) Current connection to a separate ground current transformer (summation current
transformer or core balance current transformer) for the No.2 zero sequence current
input of this relay.
2.
Voltage connections examples
A
B
C
52
52
52
Where:
(1) Voltage connections to three star-connected voltage transformers with open-delta
windings and additionally to any phase voltage (for synchronism check).
(2) Voltage connections to three star-connected voltage transformers with open-delta
windings and additionally to any phase-to-phase voltage (for synchronism check).

6.6.2 Current Transformer Requirements

CT Requirements
Rated primary current "I
--
According to the rated current or maximum load current of primary apparatus
Rated continuous thermal current "I
--
According to the maximum load current
Rated short-time thermal current "I
--
According to the maximum fault current
Rated secondary current "I
--
Accuracy limit factor "K
--
I
Rated primary current (amps)
pn
I
Rated continuous thermal current (amps)
cth
6-12
05
Ux
06
Uxn
01
Ua
02
Ub
03
Uc
04
Un
07
U0
08
U0n
(1)
Figure 6.6-3 Voltage connection examples
":
pn
":
cth
" and rated dynamic current "I
th
"
sn
":
alf
Date: 2014-04-08
A
B
C
52
52
52
(2)
":
dy n
05
Ux
06
Uxn
01
Ua
02
Ub
03
Uc
04
Un
07
U0
08
U0n
PCS-9611 Feeder Relay