General Specification; Electrical Specifications - NR Electric PCS-9611 Instruction Manual

Feeder relay
Hide thumbs Also See for PCS-9611:
Table of Contents

Advertisement

2.1 General Specification

2.1.1 Electrical Specifications

2.1.1.1 Power Supply
Standard
Rated voltage
Variation
Permissible ripple voltage
Traditional AC inputs
Burden
Digital AC inputs
2.1.1.2 Analog Current Input Ratings
Phase rotation
Rated frequency (fn)
Nominal range
Application object
Rated current (In)
Linear to
continuously
Thermal
for 10s
withstand
for 1s
capability
for half a cycle
Burden (@ In)
2.1.1.3 Analog Voltage Input Ratings
Phase rotation
Rated frequency (fn)
Nominal range
Rated voltage (Un)
Linear to
continuously
Thermal
withstand
10s
capability
1s
Burden
2.1.1.4 Binary Input
Binary input number
Rated voltage
Rated current
Pickup voltage
"ON" value voltage
PCS-9611 Feeder Relay
IEC60255-11: 2008
30Vdc, 110/125Vdc, 220/250Vdc, 110/220Vac
80% ~ 120%
Ma x 15% of the rated voltage (DC power supply)
< 15W @ Quiescent condition; < 20W @ Operating condition
< 20W @ Quiescent condition; < 25W @ Operating condition
ABC
50Hz, 60Hz
fn ± 5Hz
For protection
1A
30×In
30×In
3×In
3×In
30×In
30×In
100×In
100×In
250×In
250×In
< 0.15VA/phase
< 0.25VA/phase
ABC
50Hz, 60Hz
fn ± 5Hz
100V ~ 130V (phase-to-phase voltage)
130V
130V
200V
250V
< 0.10VA / phase
Up to 38
24V
30V
48V
1.20mA
1.50mA
2.40mA
55% ~ 70% rated voltage
70% ~ 120% rated voltage
Date: 2014-04-08
For metering
5A
1A
2×In
2×In
12×In
30×In
75×In
< 0.20VA/phase
110V
125V
1.10mA
1.25mA
2 Technical Data
5A
2×In
2×In
12×In
30×In
75×In
< 0.40VA/phase
220V
250V
2.20mA
2.50mA
2-1