7.3.7 Cold Load Pickup Settings

The cold load pickup logic settings (in the submenu "CLP Settings") are used to determine the
characteristic of the cold load pickup logic.
All the settings of the cold load pickup logic are listed in the following table
No.
Menu text
1
CLP.Opt_LogicMode
2
CLP.t_Cold
3
CLP.t_Rst
4
CLP.t_ShortRst
5
CLP.En
6
50/51P1.CLP.IMult
7
50/51P1.CLP.t_Op
8
50/51P2.CLP.IMult
9
50/51P2.CLP.t_Op
10
50/51P3.CLP.IMult
11
50/51P3.CLP.t_Op
12
50/51P4.CLP.IMult
13
50/51P4.CLP.t_Op
14
50/51P4.CLP.TMS
15
50/51G1.CLP.IMult
16
50/51G1.CLP.t_Op
PCS-9611 Feeder Relay
The logic setting for the broken conductor
protection
The output matrix setting of the broken conductor
protection
Explanation
The setting for selecting the cold load condition
The time setting for ensuring the cold load
condition is met
The time setting for resetting the cold load pickup
logic
The time setting for fast resetting the cold load
pickup logic
The logic setting of the cold load pickup logic
function
The multiple setting of the stage 1 overcurrent
protection when CLP is active
The time setting of the stage 1 overcurrent
protection when CLP is active
The multiple setting of the stage 2 overcurrent
protection when CLP is active
The time setting of the stage 2 overcurrent
protection when CLP is active
The multiple setting of the stage 3 overcurrent
protection when CLP is active
The time setting of the stage 3 overcurrent
protection when CLP is active
The multiple setting of the stage 4 overcurrent
protection when CLP is active
The time setting of the stage 4 overcurrent
protection when CLP is active
The time multiplier setting of the IDMT overcurrent
protection when CLP is active
The multiple setting of the stage 1 zero sequence
overcurrent protection when CLP is active
The time setting of the stage 1 zero sequence
overcurrent protection when CLP is active
Date: 2014-04-08
7 Settings
0~1
1
0x00000 ~
1
0xFFFFF
Range
Step
1~2
1
0~4000s
0.001s
0~4000s
0.001s
0~600s
0.001s
0~1
1
1.00~10.00
0.001
0~100s
0.001s
1.00~10.00
0.001
0~100s
0.001s
1.00~10.00
0.001
0~100s
0.001s
1.00~10.00
0.001
0~100s
0.001s
0.05~100.0
0.001
1.00~10.00
0.001
0~100s
0.001s
7-15