7.6.1 Device Settings

The device settings (in the submenu "Device Settings") are used for setting the operation
parameters of this device.
The following table lists all the communication parameters.
No.
Menu text
9
HDR_EncodeMode
10
Opt_Caption_103
11
B07.Un_BinaryInput
12
Opt_CT_Measmt
13
En_MDisk
NOTE!
1.
The setting [Opt_Caption_103] is used for selecting the language of the group caption when
the IEC60870-5-103 protocol is adopted. If it is set as "1", the group caption language is
Chinese; if it is set as "2", the group caption language is English; and if it is set as "0", the
group caption language is the language which is selected through the submenu "Language".
2.
The setting [B07.Un_BinaryInput] is used for selecting the rated voltage of the binary input.
Setting Value
Rated Voltage
3.
The setting [Opt_CT_Measmt] is used for selecting the source of the metering current values.
If it is set as "1", the calculation of the metering current values is based on the sampled data
from the dedicated metering current transformers of this relay; and if it is set as "0", the
calculation of the metering current values is based on the sampled data from the protection
current transformers of this relay.
The setting [En_MDisk] is used to decide whether the moveable disk is in service. "1"(Enable):
4.
Use moveable disk to realize the backup and recovery function; "0"(Disable): Moveable disk
will be disabled. A moveable disk is implemented on the main CPU module to backup and
restore programs, settings and configurations.

7.6.2 Communication Settings

The communication settings (in the submenu "Comm Settings") are used for communication with
substation monitoring system, substation controlling system or remote SCADA.
The following table lists all the communication parameters.
No.
Menu text
1
IP_LAN1
2
Mask_LAN1
PCS-9611 Feeder Relay
Explanation
The encoding type of the HDR waveform file, it is
only reserved for the manufacturer
The language of the group caption when the
IEC60870-5-103 is adopted
The rated voltage value of the binary input
The source of the metering current values
The logic setting of the moveable disk
0
1
24V
48V
Explanation
The IP address of the No.1 Ethernet port
The mask code of the No.1 Ethernet port
Date: 2014-04-08
2
3
110V
220V
7 Settings
Range
Step
0~1
1
0~2
1
0~5
1
0~1
1
0~1
1
4
5
30V
125V
Range
000.000.000.000
~255.255.255.255
7-31