Connection Examples - NR Electric PCS-9611 Instruction Manual

Feeder relay
Hide thumbs Also See for PCS-9611:
Table of Contents

Advertisement

NOTE! If the NR4422-4I4U module is adopted, the No.2 zero sequence overcurrent
protection, the sensitive earth fault protection and the zero sequence overvoltage
protection will be disabled automatically, and the relevant information will be hidden.

6.6.1 Connection Examples

Some connection examples of the current transformers and voltage transformers which are
supported by this relay are shown in this section. If one of the analog inputs has no input in a
practical engineering, the relevant input terminals should be disconnected.
1.
Current connections examples
A
B
C
A
B
C
Where:
(1) Current connections to three current transformers with a star-point connection for ground
current (zero sequence current or residual current).
(2) Current connections to three current transformers with a separate ground current
transformer (summation current transformer or core balance current transformer) .
(3) Current connections to two current transformers with a separate ground current
transformer (summation current transformer or core balance current transformer) , only
for ungrounded or compensated networks.
(4) Current connection to a core balance neutral current transformer for sensitive ground
fault detection, only for ungrounded or compensated networks.
PCS-9611 Feeder Relay
11
Ia
12
Ian
13
Ib
14
Ibn
15
Ic
16
Icn
17
I01
18
I01n
(1)
11
Ia
12
Ian
13
Ib
14
Ibn
15
Ic
16
Icn
17
I01
18
I01n
(2)
Figure 6.6-2 Current connection examples
Date: 2014-04-08
A
B
C
(3)
(4)
(5)
6 Hardware
11
Ia
12
Ian
13
Ib
14
Ibn
15
Ic
16
Icn
17
I01
18
I01n
19
I0s
20
I0sn
09
I02
10
I02n
6-11