9 Configurable Function

9.3 Configurable Information

9.3.1 Configurable Input Signals

All the configurable input signals of this relay are listed in following table.
No.
Input Signal
1
BI_52b
2
BI_52a
3
Sig_MCB_VT
4
Ctrl.In_EnCtrl
5
Ctrl.In_Unblock
6
Ctrl1.In_ManOpn
7
Ctrl1.In_ManCls
8
Ctrl1.In_ManSynChk
9
Ctrl1.In_ManDdChk
10
BI_LowPres_Trp
11
BI_LowPres_Cls
12
50BF.In_Init
13
BI_RstTarg
14
Alm_Maintenance
15
BI_TrigDFR
16
27P1.OnLoad
17
27P2.OnLoad
18
50/51P1.En1
19
50/51P1.Blk
20
50/51P2.En1
21
50/51P2.Blk
22
50/51P3.En1
23
50/51P3.Blk
24
50/51P4.En1
25
50/51P4.Blk
26
50/51P5.En1
27
50/51P5.Blk
28
50/51P6.En1
29
50/51P6.Blk
30
50/51Q1.En1
9-2
The binary input of the auxiliary normally closed contact of the circuit
breaker
The binary input of the auxiliary normally opened contact of the circuit
breaker
The binary signal for inputting the state of the VT's miniature circuit
breaker
The binary signal for enabling the remote control function
The binary signal for unlocking the interlock control function
The binary input for inputting the manual tripping signal
The binary input for inputting the manual closing signal
The binary signal for enabling synchronism check of manual closing
The binary signal for enabling dead check of manual closing
The binary input of the tripping low pressure signal
The binary input of the closing low pressure signal
The initiation signal of the breaker failure protection
The binary input of the signal resetting signal
The device maintenance supervision signal
The binary input of the triggering oscillography signal
The binary signal for inputting the system on load state of the stage 1
undervoltage protection
The binary signal for inputting the system on load state of the stage 2
undervoltage protection
The binary signal for enabling the stage 1 overcurrent protection
The binary signal for blocking the stage 1 overcurrent protection
The binary signal for enabling the stage 2 overcurrent protection
The binary signal for blocking the stage 2 overcurrent protection
The binary signal for enabling the stage 3 overcurrent protection
The binary signal for blocking the stage 3 overcurrent protection
The binary signal for enabling the stage 4 overcurrent protection
The binary signal for blocking the stage 4 overcurrent protection
The binary signal for enabling the stage 5 overcurrent protection
The binary signal for blocking the stage 5 overcurrent protection
The binary signal for enabling the stage 6 overcurrent protection
The binary signal for blocking the stage 6 overcurrent protection
The binary signal for enabling the stage 1 negative sequence
overcurrent protection
Date: 2014-04-08
Description
Default
B07.BI_08
B07.BI_09
B07.BI_03
B07.BI_07
B07.BI_04
B07.BI_06
PCS-9611 Feeder Relay