7.1 Overview

The settings are used to determine the characteristic of each protective element and operation
mode of the relay. It is necessary to configure the settings of this relay according to engineering
demands before putting this relay into service. If the settings are not configured correctly, this
relay maybe works abnormally (such as communication interruption, printing out unexpected
codes etc.), it also can lead to much more serious accident (such as unwanted operation, missing
operation) sometimes.
The settings of this relay include system settings, protection settings, communication settings and
miscellaneous settings. The user can configure these settings or parameters manually (see
Section 8.2.6.2). Remote modification is also supported (IEC61850, IEC60870-5-103 or DNP3.0
interface, see Chapter 10 for the details about these protocols).
NOTE! If a CPU module is replaced, it is necessary to configure all the settings again
according to the configuration of the CPU module which is replaced.

7.2 System Settings

The system settings (in the submenu "System Settings") are mainly used to set the rated value
of VT and CT.
The following table lists all the system parameters.
No.
Menu text
1
Acti ve_Grp
2
Opt_SysFreq
3
PrimaryEquip_Name
4
Prot.I1n
5
Prot.I2n
6
Measmt.I1n
7
Measmt.I2n
8
Neu1.I1n
9
Neu1.I2n
10
Neu2.I1n
11
Neu2.I2n
12
SEF.I1n
13
SEF.I2n
14
Prot.U1n
15
Prot.U2n
16
Syn.U1n
17
Syn.U2n
18
Delt.U1n
PCS-9611 Feeder Relay
Explanation
The active setting group number
Select the rated system frequency: "0", 50Hz; "1", 60Hz
The name of the protected primary equipment
Rated primary value of protection phase CT
Rated secondary value of protection phase CT
Rated primary value of metering phase CT
Rated secondary value of metering phase CT
Rated primary value of the No.1 zero sequence CT
Rated secondary value of the No.1 zero sequence CT
Rated primary value of the No.2 zero sequence CT
Rated secondary value of the No.2 zero sequence CT
Rated primary value of sensitive zero sequence CT
Rated secondary value of sensitive zero sequence CT
Rated primary value of protection VT
Rated secondary value of protection VT
Rated primary value of synchro-check VT
Rated secondary value of synchro-check VT
Rated primary value of zero sequence VT
Date: 2014-04-08
7 Settings
Range
Step
1 ~ 10
1
0~1
1
1~7 characters
0~20000A
1A
1/5A
4A
0~20000A
1A
1/5A
4A
0~20000A
1A
1/5A
4A
0~20000A
1A
1/5A
4A
0~20000A
1A
1/5A
4A
0.1~500.0kV
0.001kV
100~200V
0.001V
0.1~500.0kV
0.001kV
10~200V
0.001V
0.1~500.0kV
0.001kV
7-1