Protection Settings - NR Electric PCS-9611 Instruction Manual

Feeder relay
Hide thumbs Also See for PCS-9611:
Table of Contents

Advertisement

7 Settings
19
Delt.U2n
20
Opt_3I0
21
Opt_3U0
22
Opt_PwrDir
NOTE!
1.
The system settings are related to the protection activities, thus it is necessary to configure
theses settings according to actual conditions.
2.
The setting [Opt_3I0] is used to select the No.1 zero sequence current source. Setting the
value of [Opt_3I0] as "1" means that the No.1 zero sequence current is self-calculated, and
setting the value as "0" means that the No.1 zero sequence current is derived from specific
zero sequence CT. The default value is "0" when the equipment is delivered.
3.
The setting [Opt_3U0] is used to select the zero sequence voltage source. Setting the value
of [Opt_3U0] as "1" means that zero sequence voltage is self-calculated, and setting the
value as "0" means that zero sequence voltage is derived from specific broken delta VT.
4.
The setting [Opt_PwrDir] is used to select the power measurement mode.
[Opt_PwrDir]
0
1
2
3

7.3 Protection Settings

The protection settings (in the submenu "Prot Settings") are used to decide the characteristics of
the protective elements. There are up to 10 groups of protection settings in this relay.
NOTE! Following items should be considered before modifying the protection settings.
1.
Before configuring the settings, the setting group must be configured firstly.
2.
When a certain setting is of no use, in case of over-elements (such as overcurrent, residual
overcurrent), set the value as upper limit; in case of under-elements (such as under frequency,
under voltage), set the value as lower limit; set the corresponding time as 100s and disable
corresponding protection element and de-energize the corresponding binary input.
3.
In general, for switch onto fault protection and accelerated protection, it is necessary to set a
time delay from decades to 100ms. Thanks to there is no 100ms time delay in the numerical
7-2
Rated secondary value of zero sequence VT
Zero sequence current is self calculated
0:from neutral CT 1:self calculated
Zero sequence voltage is self calculated
0:from neutral VT 1:self calculated
Power Measurement Mode
Active Power
To line
+W
-W
+W
-W
Date: 2014-04-08
Lagging reactive power
To busbar
To line
-W
+Var
+W
+Var
-W
-Var
+W
-Var
10~200V
0.001V
0~1
1
0~1
1
0~3
1
To busbar
-Var
-Var
+Var
+Var
PCS-9611 Feeder Relay