7 Settings
9
MR3.OutMap
10
MR4.t_Op
11
MR4.En
12
MR4.OutMap

7.3.16 Dead Zone Protection Settings

The dead zone protection settings (in submenu "DZ Settings") are used to determine the
characteristic of the dead zone protection.
All the settings of the dead zone protection are listed in the following table.
No.
Menu text
1
50DZ.I_Set
2
50DZ.t_Op
3
50DZ.En
4
50DZ.OutMap

7.3.17 Undercurrent Protection Settings

The undercurrent protection settings (in submenu "UC Settings") are used to determine the
characteristic of the undercurrent protection.
All the settings of the undercurrent protection are listed in the following table.
No.
Menu text
1
37.I_Set
2
37.t_Op
3
37.En
4
37.OutMap

7.3.18 Supervision Element Settings

The supervision element settings (in the submenu "Superv Settings") are used to determine the
parameters of the supervision element.
All the settings of the supervision element are listed in the following table.
No.
Menu text
1
CTS.3I0_Set
2
CTS.3U0_Set
3
CTS.En
7-24
The output matrix setting of the No.3 mechanical
protection
The time setting of the No.4 mechanical
protection
The logic setting of the No.4 mechanical
protection
The output matrix setting of the No.4 mechanical
protection
Explanation
The current setting of the dead zone protection
The time setting of the dead zone protection
The logic setting of the dead zone protection
The output matrix setting of the dead zone
protection
Explanation
The current setting of the undercurrent protection
The time setting of the undercurrent protection
The logic setting of the undercurrent protection
The output matrix setting of the undercurrent
protection
Explanation
The threshold current setting of the CTS element
The threshold voltage setting of the CTS element
The logic setting of the CTS element
Date: 2014-04-08
0x00000 ~
1
0xFFFFF
0~4000s
0.001s
0~1
1
0x00000 ~
1
0xFFFFF
Range
Step
0.1In~5.0In
0.001A
0~100s
0.001s
0~1
1
0x00000 ~
1
0xFFFFF
Range
Step
0.1In~1.0In
0.001A
0~100s
0.001s
0~1
1
0x00000 ~
1
0xFFFFF
Range
Step
0.05In~30In
0.001A
0.01~120V
0.001V
0~1
1